DIN Standards Committee Valves
Building valves - Expansion valves - Tests and requirements
Abstract
This document specifies dimensions, materials and performance requirements (including methods of test) for expansion valves, of nominal sizes from DN 15 to DN 32, having working pressures1) from 0,1 MPa (l bar) to 1,0 MPa (10 bar). Expansion valves are intended for fitting to the cold potable water supply of storage water heaters, having a maximum distribution temperature of 95 °C, for all energy sources. Expansion valves do not control the temperature and alone do not constitute the protection required for storage water heaters. Expansion valves limit pressure, in the water heaters to what they are fitted, that is produced by thermal expansion of the water. NOTE The use of the device specified in this document does not override the need to use controls (e.g. thermostats and cut-outs) which act directly on the power sources of water heaters (for more information see Annex A).
Begin
2025-05-13
WI
00164780
Planned document number
prEN 1491 rev
Responsible national committee
NA 003-02-02 AA - Valves for potable water supply in buildings
Responsible european committee
CEN/TC 164/WG 14 - Valves and fitting for buildings and devices to prevent pollution by backflow
previous edition(s)
Building valves - Expansion valves - Tests and requirements
2022-07